Intuitive Local Operator Interface with dedicated keys enhance ease of use and enables instant access to all diagnostic information. Ideal for hazardous environments or difficult-to-reach locations.
Accuracy: Up to ±0.15% of volumetric flow rate accuracy over 13:1 flow turndowns, ±0.25% over 40:1 flow turndown.
Diagnostic: In Situ Meter Verification, Grounding & Wiring Fault Detection, High Process Noise Detection, Tunable Empty Pipe Detection, Transmitter Fault Detection, Sensor Fault Detection
Compatibility: All Rosemount manufactured Sensors: 8705, 8711, 8721, 8707Universal capabilities allow E-Series transmitters to be compatible with AC and DC powered sensors from other manufacturers.
Power Supply: 90-250 VAC, 50-60 Hz or 12-42 VDC.
Power consumption: 15 W maximum - DC40 VA maximum - AC
Enclosure Rating: 8712E: Type 4x, IP66