Danfoss 137L1088 FC-202N200T4E5MH2TGC3XXSXXXXA0B2CXXXXD0

Write a Review
$15,518.23
SKU:
137L1088
Request a Quote

Frequency converter
FC-202N200T4E5MH2TGC3XXSXXXXA0B2CXXXXD0
VLT® AQUA Drive FC-202
(N200) 200 KW / 300 HP, Three phase
380 - 480 VAC, IP54/Type 12+main shield
RFI Filter
Safe Stop
Graphical Loc. Cont. Panel
Coated PCB, Mains Disconnect + Fuse
Latest release std. SW.
Frame: D7H
No C1 option, MCB-107 24V DC backup
PROFIBUS DP MCA 101, MCB-112 PTC Therm. Card
ATEX: II (2) G [Ex eb Gb] [Exdb Gb] / II (2) D [Ex tb Db]
Gross weight 200.3 kg
Net weight 200 kg
Volume 0 l
EAN 5715253481173
VLT® AQUA DRIVE FC 200 SERIES
Product View (Switch) GLBL Global (Standard)
Product Group FC- VLT® AQUA Drive FC-
Series 202 202
Power Rating N200 (N200) 200 KW / 300 HP
Phase T Three phase
Mains Voltage 4 380 - 480 VAC
Enclosure E5M IP54/Type 12+main shield
RFI Filter H2 RFI Filter
Brake - Safe Stop T Safe Stop
LCP G Graphical Loc. Cont. Panel
Coating PCB C Coated PCB
Mains Option 3 Mains Disconnect + Fuse
Adaptation A X Standard Cable Entries
Adaptation B X No adaptation
Software Release SXXX Latest release std. SW.
Software Language Pack X Standard Language Pack
A Option A0 PROFIBUS DP MCA 101
B Option B2 MCB-112 PTC Therm. Card
C0 Option MCO CX No C0 option
C1 Option X No C1 option
C Option Software XX No software option
D Option D0 MCB-107 24V DC backup
Frame Size D7H D7H
Typecode Part 1 FC-202N200T4E5MH2TGC
Typecode Part 2 3XXSXXXXA0B2CXXXXD0
Product Catalog NO_VIEW NO VIEW
Power 150% (HO) [KW] 160
Power 110% (NO) [KW] 200
Height [mm] 1978,0
Width w/ no C options [mm] 420,0
Depth [mm] 386,0
Depth with Option A/B [mm] 386,0
kVA 274
Power Loss NO [W] 4116
Power Loss NO [W] 3569
Power Loss HO [W] 3093
Power Loss HO [W] 2872
Continuous Current (NO) [A] 395
Intermittent Current (NO) [A] 435
Continuous Current (NO) [A] 361
Intermittent Current (NO) [A] 397
Continuous Current (HO) [A] 315
Intermittent Current (HO) [A] 472
Continuous Current (HO) [A] 302
Intermittent Current (HO) [A] 453
ATEX Marking 1 ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2 db Gb] / II (2) D [Ex tb Db]
Calculated Gross Weight [kg] 200.3
Calculated Net Weight [kg] 200
ECCN EU X.A.I.003
ECCN US 3A999
Plant from Orderline F605
Vendor ERR01 Cannot Determine Vendor
Recommended Factory ERR01 Cannot Determine Vendor
Modelcode01 FC-202N200T4E5MH2TGC