The Flexim FLUXUS F532 TE is a compact thermal energy meter with integrated heat flow calculation for water and all water-glycol mixtures. The FLUXUS F532 Thermal Energy is specially designed for heating and cooling measurements in industry and building applications. Based on the established transit time difference method, the volume flow is measured non-intrusively with ultrasound, and the supply and return temperatures are registered via 2 temperature inputs. Totalizers for total thermal energy are also included. Offering USB and LAN interfaces and serves the common communication interfaces Modbus TCP, Modbus RTU, BACnet MS/TP, BACnet IP and M-Bus.
Fluid Type: Water and water/glycol mixtures
Accuracy: Measurement uncertainty of the measuring system (volumetric flow rate): ±0.3 of reading ±0.005 m/s ( ±0.02 ft/s)Measurement uncertainty at the measuring point (volumetric flow rate):: ±1 % of reading ±0.005 m/s (±0.02 ft/s)
Repeatability: 0.15 % of reading ±0,005 m/s (±0.02 ft/s)
Flow channels: 1
Range: Flow Velocity Range: 0.01...25 m/s (0.03 to 82 ft/s)
Certifications/approvals: Ordloc (FM)
Power supply: 90 to 250 VAC / 50 to 60 Hz11 to 32 VDC
Pipe size: 10…2400 mm (0,39…94,5 inch)
Pressure range: -
Temperature range (media): -40 to +130°C (-40 to 266 °F)
Output: 4-20mA active/passive according to NAMUR NE43pulse/frequency/binary
Input: Temperature
Communication protocol: Modbus RTUBACnet MS/TPHART®Modbus TCPM-BusBACnet IPUSBLAN
System configuration and installation: For more detailed Information please download the Technical Specifications